Basic parameters | |
Power Supply | 20~35V DC |
Power protection | Power backconnect protection |
Consumption current (24V power supply, 20mA output) | ≤95mA |
Response Time | ≤1.5ms, 90% of the final value |
Transmission accuracy (20℃, 4~20mA) | 0.1%F.S. (Typical value: 0.05%F.S.) |
The use of ambient temperature | -20℃~+60℃ |
Connected field equipment and the area where it is located | Two, three wire system transmitter, current source; This product is suitable for Rosemount, EJA, ABB, Fisher, Honeywell,FOXBORO and other products) 0 zone, 1 zone, 2 zone, ⅡA, ⅡB, ⅡC, T4 ~ T6 danger zone |
Hazard side input | |
Input | 4 ~ 20mA, HART digital signal |
Voc | ≤28V |
Distribution voltage at 20mA current | ≥16V |
Safe side output | |
IOUT | 4 ~ 20mA, HART digital signal |
RL | RL≤500Ω |
Output Impedance | ≥1MΩ |
DT-8811接线图